Categories
Categories
Warehouse: United States

Potter IDC-6 Initiating Device Circuit Expander

IDC-6 EXPANDER / PFC-4064
Product images for Potter IDC-6 Initiating Device Circuit Expander. 2 image(s) available. Click on image to view full size.

Key Features

  • Expand system capacity quickly: adds six supervised initiating inputs per module to support growing fire and security monitoring needs
  • Scalable and flexible: install up to 31 IDC-6 modules for large systems without rewiring main panels
  • Simple, secure mounting: ships with exclusive Stacker Bracket for fast, service-friendly installation in panel or expander cabinets
  • Broad compatibility: supports 2‑wire smoke detectors and integrates with IPA/AFC/ARC/PFC series panels for unified surveillance and alarm control
  • Reliable supervised circuits: power‑limited, supervised inputs help maintain NFPA 72 compliance and reduce false alarms

Quick Specifications

Product Model
IDC-6
Sector
Fire
Brand Name
Potter Electric Signal, LLC
Product Name
IDC-6 Initiating Device Circuit Expander
View Full Technical Specifications

Frequently Bought Together

This Item
Potter IDC-6 Initiating Device Circuit Expander

Potter IDC-6 Initiating Device Circuit Expander

$387.83

Frequently Bought Together (4 items)

5 items selected

Total: $2,145.08

Product Information Tabs

Overview

Add reliable, supervised initiating capacity to your fire and security systems with the Potter Electric Signal, LLC IDC-6 Initiating Device Circuit Expander. Designed for commercial and industrial fire alarm applications, the IDC-6 delivers six monitored IDC inputs per module — ideal for integrating additional 2‑wire smoke detectors, pull stations, waterflow switches or supervisory devices into a single control network. Each module communicates over the p-Link RS-485 bus (4‑wire connection) and can be mounted inside the main control panel, pSN-1000 supply, or AE-series expander cabinets for flexible placement. Support up to 31 IDC-6 modules to scale large installations while keeping wiring simplified; p-Link runs are power‑limited and supervised with a recommended maximum local p-Link distance of 20 feet. Engineered for dependable operation in typical equipment rooms (operating range to 120°F), the IDC-6 helps streamline installation, maintenance and code-compliant monitoring to protect life and property. For dependable expansion of your fire alarm and security surveillance network, add the IDC-6 to your next system upgrade — contact your rep or order online.

Features

  • Expand system capacity quickly: adds six supervised initiating inputs per module to support growing fire and security monitoring needs
  • Scalable and flexible: install up to 31 IDC-6 modules for large systems without rewiring main panels
  • Simple, secure mounting: ships with exclusive Stacker Bracket for fast, service-friendly installation in panel or expander cabinets
  • Broad compatibility: supports 2‑wire smoke detectors and integrates with IPA/AFC/ARC/PFC series panels for unified surveillance and alarm control
  • Reliable supervised circuits: power‑limited, supervised inputs help maintain NFPA 72 compliance and reduce false alarms
General Information
Sector Fire
Brand Name Potter Electric Signal, LLC
Manufacturer Potter Electric Signal, LLC
Product Name IDC-6 Initiating Device Circuit Expander
Product Type Initiating Device Circuit Expander
Manufacturer Part Number IDC-6
Environmental Conditions
Maximum Operating Temperature 120°F (48.9°C)
Minimum Operating Temperature 32°F (0°C)
Physical Characteristics
Depth 1.1"
Width 4"
Height 6"
Miscellaneous
Compatibility IPA Series AFC/ARC Series PFC-4064
Country of Origin US